ABB  Art.Nr: 15433177334091

MS116-10 Motor protection circuit breaker trip class 10A, 6.3 ... 10 A

Regular price
Regular price € 60,49 inkl. USt.
€ 50,41 exkl. USt.

€ 57,47 inkl. USt.

up to −7 % with the Black Friday offer. 5% deducted automatically in your cart, + 2% for prepayment with code VORKASSE2.

Offer ends in00 days00 hrs00 min00 sec
Verfügbarkeit wird geladen …
WhatsApp Sofortberatung Jetzt online Persönliche Beratung direkt vom Fachmann – Antwort meist in wenigen Minuten.

The MS116 motor starter protector with thermal and electromagnetic protection represents a compact and economical series for motor protection up to 15 kW (400 V) with a module width of 45 mm. The temperature-compensated device features a rotary handle operation with a clear I/0 switching position indicator. The rotary handle can be locked in the 0-position with a locking device. Auxiliary and signal contacts, as well as undervoltage and shunt trips, can be mounted without tools. 3-phase busbars for 65 A or 100 A and infeed blocks for 25 mm² or 35 mm² allow the common power supply of several motor starter protectors. Protective enclosures and accessories for control cabinet and door mounting complete the range.

Installation anfragen
Montage • Elektro • Inbetriebnahme
Wir bieten die Installation deiner Photovoltaikanlage durch unser Team sowie durch ausgewählte Partnerbetriebe an. Gemeinsam sorgen wir für eine fachgerechte Montage, Elektroinstallation und zuverlässige Inbetriebnahme.
Installation anfragen
Datenblatt
Hinweis: Der Link kann je nach Hersteller direkt einen Download starten.
Öffnen / Download

Technische Parameter

Setting range of the instantaneous short-circuit release 150..150 A Rated permanent current Iu 10 A
With integrated auxiliary switch No Degree of protection (IP) IP20
Release technique thermomagnetic With integrated undervoltage release No
Rated operational voltage 690..690 V Type of control element Rotary knob
Depth 85.6 mm Overload release current setting 6.3..10 A
Rated ultimate short-circuit breaking capacity Icu at 400 V, AC 75 kA Height 90 mm
Device construction Complete device in housing Number of poles 3
With thermal overload protection Yes Phase failure sensitive Yes
Width 45 mm Rated operational power at AC-3, 230 V 4 kW
Power loss 7.2 W Type of electrical connection main circuit Screw connection
Rated operational power at AC-3, 400 V 4 kW